Neutral Earthing Transformer
Neutral Earthing Transformer

Neutral Earthing Transformer

MOQ : 1 Unit

Neutral Earthing Transformer Specification

  • High Voltage
  • 11 kV
  • Cooling Type
  • ONAN (Oil Natural Air Natural)
  • Operating Temperature
  • -10C to +45C
  • Load Loss
  • 420 W
  • Voltage Booster Type
  • Zig-Zag Transformer
  • Low Voltage
  • 433 V
  • Capacity
  • 50 kVA
  • Dimension (L*W*H)
  • 950 x 750 x 1150 mm
  • Rated Voltage
  • 11 kV/433 V
  • Standard
  • IS 2026 / IEC 60076
  • Coil Material
  • Copper
  • Product Type
  • Neutral Earthing Transformer
  • Material
  • Copper
  • Output
  • Product wise
  • Frequency (MHz)
  • 50 Hertz (HZ)
  • Efficiency
  • 99.9%
  • Phase
  • Three Phase
  • Usage
  • Neutral Earthing in electrical power systems
  • Coil Structure
  • Toroidal / Layer wound
  • Coil Number
  • Two windings (Primary & Secondary)
  • Power Scope
  • For safe earthing of distribution transformer or generator sets
  • Weight
  • 250 kg (approx)
  • Maximum Altitude
  • Up to 1000 m above sea level
  • Impedance Voltage
  • 4.5%
  • Paint Type
  • Epoxy powder coated
  • Core Type
  • Laminated Core
  • Dielectric Strength
  • 35 kV (Power Frequency Withstand)
  • Degree of Protection
  • IP23
  • Mounting Type
  • Floor Mounted
  • Earthing Terminal
  • Provided as per standard
  • Service Duty
  • Continuous
  • Shipping Condition
  • Filled with Transformer Oil
  • Insulation Class
  • Class F
 

Neutral Earthing Transformer Trade Information

  • Minimum Order Quantity
  • 1 Unit
  • Supply Ability
  • 100 Units Per Month
  • Delivery Time
  • 2-3 Months
 

About Neutral Earthing Transformer

Supported by wide distribution network & panel of well-trained personnel, we are noted as the cardinal manufacturer and exporter of Neutral Earthing Transformer. Our expert procuring agent procures supreme quality components and materials from certified vendors of the market for manufacturing these earthing transformers in compliance with industrial standards. Perfect for providing possibility for neutral earthing, this transformer is widely used to create a neutral point in a three-phase system.

Features of Neutral Earthing Transformer:

  • Rust proof finish
  • Easy installation
  • Smooth working

Further Details:

Earthing up to 2 MVA 33 kV.

Neutral Earthing transformers are normally provided in 3-phase system, which is without neutral and earth fault protection.

It has zig-zag (interstar) winding to achieve the required zero phase impedance. In addition an auxiliary winding can also be provided to meet the requirement of auxiliary power supply.

ONAN / ONAF cooling with conventional pressed steel radiators. The range includes up to 33 KV systems and as per the site requirements.

A Earthing ( zigzag ) transformer is a special purpose transformer with a zigzag or interconnected star winding connection, such that each output is the vector sum of two phases offset by 120 Degree .

Its applications are for the creation of a missing neutral connection from an un-grounded, 3-phase system to permit the grounding of that neutral to an earth reference point and also harmonic mitigation, as it can suppress triplet (3rd, 9th, 15th, 21st, etc.) harmonic currents, to supply 3-phase power as an auto transformer (serving as the primary and secondary with no isolated circuits), and to supply non-standard phase-shifted 3-phase power.

Nine-winding three-phase transformers, typically have 3 primaries and six identical secondary windings which be used in zigzag winding connection as pictured. As with the conventional delta or wye winding configuration three-phase transformer, a standard stand-alone transformer containing only six windings on three cores can also be used in zigzag winding connection, such transformer sometimes being referred to as a zigzag bank. In all cases, six or nine winding, the first coil on each zigzag winding core is connected contrariwise to the second coil on the next core. The second coils are then all tied together to form the neutral and the phases are connected to the primary coils. Each phase, therefore, couples with each other phase and the voltages cancel out. As such, there would be negligible current through the neutral point, which can be tied to ground.

Each of the three limbs are split into two sections. The two halves of each limb have the equal number of turns and theyre wound in opposite directions. With the neutral grounded, during a phase to ground short fault, a third of current returns to the fault current and the remainder must go through two of the three phases when used to derive a grounding point from a delta source.

If one phase, or more, faults to earth, the voltage applied to each phase of the transformer is no longer in balance fluxes in the windings no longer oppose. (Using symmetrical components, this is Ia0 = Ib0 = Ic0.) Zero sequence (earth fault) current exists between the transformers neutral to the faulting phase. The purpose of a zigzag transformer in this application is to provide a return path for earth faults on delta-connected systems. With negligible current in the neutral under normal conditions, providing the defective load will be automatically disconnected in a fault condition, an undersized transformer may be used only as short time rating is required (i.e. the transformer can only carry full rated current for, say, 60 s). Impedance should not be too low for desired maximum fault current. Impedance can be added after the secondaries are summed to limit maximum fault currents(the 3Io path).

An application example : A combination of Y (wye or star), delta, and zigzag windings may be used to achieve a vector phase shift. For example, an electrical network may have a transmission network of 110 kV/33 kV star/star transformers, with 33 kV/11 kV delta/star for the high voltage distribution network. If a transformation is required directly between the 110 kV/11 kV network an option is to use a 110 kV/11 kV star/delta transformer. The problem is that the 11 kV delta no longer has an earth reference point. Installing a zigzag transformer near the secondary side of the 110 kV/11 kV transformer provides the required earth reference point.

Application in following industries :
Chemical, Pharmaceuticals, Steel, Textile, Engineering, Plastic, Cement, Refineries, Mining, Captive Power Projects, Hydro Power Projects, Wind Mill Farms, Construction Houses, Pharma, Electrical, Electronics, Renewable Energy, Automobile.



Robust Design for Maximum Safety

This transformer offers high dielectric strength of up to 35 kV, IP23 enclosure, and premium epoxy powder coat, providing reliable insulation and environmental protection. Its floor-mounted, oil-filled structure ensures stability and longevity, while the core's laminated design enhances electrical performance and efficiency.


Standards and Compliance

Manufactured in accordance with IS 2026 and IEC 60076, this transformer integrates high-quality materials and advanced engineering, such as copper windings and toroidal/layer wound coils. These features guarantee international compliance and operational excellence in demanding electrical power applications.

FAQ's of Neutral Earthing Transformer:


Q: How is the Neutral Earthing Transformer installed and commissioned?

A: The Neutral Earthing Transformer is floor mounted and supplied filled with transformer oil for immediate commissioning. Installation requires secure placement and proper connection of high voltage (11kV) and low voltage (433V) terminals, ensuring the earthing terminal is connected as per the relevant standard.

Q: What is the primary usage of this Neutral Earthing Transformer?

A: This transformer is specifically used for the safe earthing of distribution transformers or generator sets in three-phase electrical power systems, ensuring effective grounding and improved system reliability.

Q: When should I use a Neutral Earthing Transformer with impedance voltage of 4.5%?

A: A Neutral Earthing Transformer with 4.5% impedance voltage should be used when controlled fault current limiting through the transformer is required during earth faults, helping to protect equipment and maintain stability in power distribution networks.

Q: Where can this transformer be effectively utilized?

A: It is suitable for use in substations, industrial installations, and power plants across India, especially where three-phase neutral grounding is mandated and working altitude does not exceed 1000 m above sea level.

Q: What is the process for routine maintenance of this transformer?

A: Routine maintenance involves regular oil checks, inspection of insulation integrity, tightness of electrical connections, and periodic cleaning of external surfaces. It is important to monitor the temperature to remain within -10C to +45C for optimal performance.

Q: How does this transformer benefit electrical installations?

A: This transformer ensures the system's neutral point is effectively grounded, which enhances safety, limits overvoltages, and enables protection schemes to detect and clear earth faults efficiently, with minimal load loss and very high efficiency (99.9%).

Q: What are the key standards and certifications associated with this transformer?

A: The product complies with IS 2026 and IEC 60076 standards, confirming adherence to rigorous safety, performance, and quality requirements for neutral earthing transformers in modern electrical systems.

Tell us about your requirement
product

Price:

Quantity
Select Unit

  • 50
  • 100
  • 200
  • 250
  • 500
  • 1000+
Additional detail
Mobile number

Email

More Products in Earthing Transformer Category

Industrial Earthing Transformer

Industrial Earthing Transformer

Minimum Order Quantity : 1 Unit

Efficiency : 99.9%

Frequency (MHz) : 50 Hertz (HZ)

Rated Voltage : 11 kV

Coil Material : Other , Electrolytic Grade Copper

Material : Copper

Neutral Grounding Transformer

Neutral Grounding Transformer

Minimum Order Quantity : 1 Piece

Efficiency : Up to 99%

Frequency (MHz) : 50 Hz

Rated Voltage : Up to 33 kV

Coil Material : Other , Copper / Aluminum

Material : Copper, CRGO Silicon Steel, Epoxy Resin and Mild Steel (Body)

Earthing Transformer

Earthing Transformer

Minimum Order Quantity : 1 Unit

Efficiency : 99.9%

Frequency (MHz) : 50 Hertz (HZ)

Rated Voltage : 33000 Volt (V)

Coil Material : Copper Core

Material : Copper



Back to top